You will get en email confirming that we have received your enquiry.
2 year warranty*
Worldwide delivery
Returns accepted
*Manufacturer's warranty does not apply
You will get en email confirming that we have received your enquiry.
One of our team will be in touch to confirm your part(s) specification and condition.
You will receive a comprehensive quote tailored to your specific needs.
Here is all you need to know
Part of the Simatic S7-400 programmable controller range, the 6ES7414-4HJ00-0AB0 is a CPU 414H Processor Module which features 4 Interface ports ( 1 MPI/DP, 1 DP and 2 for sync modules) as well as 768 KB memory (384 KB DATA/384 KB code). Sadly the module was made obsolete in 2010 and is no longer available through the main Siemens catalogue. Northern Industrial offer a repair service on these units as well as high quality refurbished units.
Supply voltage | |
24 V DC | Yes |
Input current | |
from backplane bus 5 V DC, typ. | 1.8 A |
from backplane bus 5 V DC, max. | 2 A |
from backplane bus 24 V DC, max. | 300 mA; Total current consumption of the components connected to the MPI/DP interfaces, but no more than 150 mA per interface |
Power loss | |
Power loss, typ. | 10 W |
Memory | |
Work memory | |
integrated | 768 kbyte; 384 KB for program; 384 KB for data |
expandable | No |
Load memory | |
expandable FEPROM | Yes; with Memory Card (FEPROM) |
expandable FEPROM, max. | 64 Mbyte |
integrated RAM, max. | 256 kbyte |
expandable RAM | Yes; with Memory Card (RAM) |
expandable RAM, max. | 64 Mbyte |
Backup | |
present | Yes |
with battery | Yes; all data |
without battery | No |
Battery | |
Backup battery | |
Backup current, typ. | 75 µA |
Backup current, max. | 860 µA |
Feeding of external backup voltage to CPU | 5 to 15 VDC |
CPU processing times | |
for bit operations, typ. | 0.1 µs |
for word operations, typ. | 0.1 µs |
for fixed point arithmetic, typ. | 0.1 µs |
for floating point arithmetic, typ. | 0.6 µs |
CPU-blocks | |
DB | |
Number, max. | 4095; DB 0 reserved |
Size, max. | 64 kbyte |
FB | |
Number, max. | 2048 |
Size, max. | 64 kbyte |
FC | |
Number, max. | 2048 |
Size, max. | 64 kbyte |
OB | |
Number, max. | see instruction list |
Size, max. | 64 kbyte |
Nesting depth | |
per priority class | 24 |
Counters, timers and their retentivity | |
S7 counter | |
Number | 256 |
Retentivity | |
adjustable | Yes |
lower limit | 0 |
upper limit | 255 |
preset | Z 0 to Z 7 |
Counting range | |
lower limit | 1 |
upper limit | 999 |
IEC counter | |
present | Yes |
Type | SFB |
S7 times | |
Number | 256 |
Time range | |
lower limit | 10 ms |
upper limit | 9990 s |
IEC timer | |
present | Yes |
Type | SFB |
Data areas and their retentivity | |
Flag | |
Number, max. | 8 kbyte |
Retentivity available | Yes; from MB 0 to MB 8191 |
Retentivity preset | MB 0 to MB 15 |
Data blocks | |
Number, max. | 4096; DB 0 reserved |
Size, max. | 64 kbyte |
Address area | |
I/O address area | |
Inputs | 8 kbyte |
Outputs | 8 kbyte |
of which distributed | |
MPI/DP interface, inputs | 2 kbyte |
MPI/DP interface, outputs | 2 kbyte |
DP interface, inputs | 6 kbyte |
DP interface, outputs | 6 kbyte |
Process image | |
Inputs, adjustable | 8 kbyte; adjustable at the expense of the code area of the RAM |
Outputs, adjustable | 8 kbyte; adjustable at the expense of the code area of the RAM |
Inputs, default | 1024 byte |
Outputs, default | 1024 byte |
Subprocess images | |
Number of subprocess images, max. | 8 |
Digital channels | |
Inputs | 65536 |
Outputs | 65536 |
Inputs, of which central | 65536 |
Outputs, of which central | 65536 |
Analog channels | |
Inputs | 4096 |
Outputs | 4096 |
Inputs, of which central | 4096 |
Outputs, of which central | 4096 |
Hardware configuration | |
Expansion devices, max. | 21 |
Multicomputing | No |
Interface modules | |
Number of connectable IMs (total), max. | 6 |
Number of connectable IM 460s, max. | 6 |
Number of connectable IM 463s, max. | 6; IM 463-2 |
Number of DP masters | |
integrated | 2 |
via IM 467 | 0 |
via CP | 10 |
Mixed mode IM + CP permitted | No; IM 467 cannot be used jointly with CP 443-5 Ext. |
via interface module | 0 |
Number of operable FMs and CPs (recommended) | |
FM | 32; Limited by number of slots and number of connections |
CP, point-to-point | 32; Limited by number of slots and number of connections |
CP, LAN | 32; Limited by number of slots and number of connections |
Slots | |
required slots | 2 |
Time of day | |
Clock | |
Hardware clock (real-time clock) | Yes |
battery-backed and synchronizable | Yes |
Operating hours counter | |
Number | 8 |
Clock synchronization | |
supported | Yes |
1. Interface | |
isolated | Yes |
Functionality | |
MPI | Yes; Default setting |
DP master | Yes |
DP slave | No |
MPI | |
Number of connections | 32 |
Transmission rate, max. | 12 Mbit/s |
Services | |
PG/OP communication | Yes |
Global data communication | No |
S7 basic communication | No |
S7 communication | Yes |
S7 communication, as client | Yes |
S7 communication, as server | Yes |
DP master | |
Number of connections, max. | 32; of which 1 reserved for PG, 1 for OP |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 32; Number of slots, max. 512 |
Services | |
PG/OP communication | Yes |
Global data communication | No |
S7 basic communication | No |
S7 communication | No |
Equidistance mode support | No |
SYNC/FREEZE | No |
Activation/deactivation of DP slaves | Yes |
Direct data exchange (slave-to-slave communication) | No |
Address area | |
Inputs, max. | 2 kbyte |
Outputs, max. | 2 kbyte |
User data per DP slave | |
Inputs, max. | 244 byte |
Outputs, max. | 244 byte |
Slots, max. | 244 |
per slot, max. | 128 byte |
2. Interface | |
isolated | Yes |
Functionality | |
DP master | Yes; Default setting |
DP slave | No |
Point-to-point connection | No |
DP master | |
Number of connections, max. | 32 |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 96 |
Services | |
PG/OP communication | Yes |
Global data communication | No |
S7 basic communication | No |
S7 communication | No |
Equidistance mode support | No |
SYNC/FREEZE | No |
Activation/deactivation of DP slaves | No |
Direct data exchange (slave-to-slave communication) | No |
Address area | |
Address area, max. | 8 kbyte |
Inputs, max. | 8 kbyte |
Outputs, max. | 8 kbyte |
User data per DP slave | |
Inputs, max. | 244 byte |
Outputs, max. | 244 byte |
Communication functions | |
PG/OP communication | Yes |
Global data communication | |
supported | No |
S7 basic communication | |
supported | No |
S7 communication | |
supported | Yes |
as server | Yes |
as client | Yes |
User data per job, max. | 64 kbyte |
S5 compatible communication | |
supported | Yes; via CP and loadable FC |
User data per job, max. | 8 kbyte |
Standard communication (FMS) | |
supported | Yes; Via CP and loadable FB |
User data per job, max. | Dependent on CP |
Number of connections | |
overall | 32 |
usable for PG communication | |
reserved for PG communication | 1 |
adjustable for PG communication, max. | 0 |
usable for OP communication | |
reserved for OP communication | 1 |
adjustable for OP communication, max. | 0 |
usable for S7 basic communication | |
reserved for S7 basic communication | 0 |
adjustable for S7 basic communication, max. | 0 |
usable for routing | |
reserved for routing | 0 |
adjustable for routing, max. | 0 |
S7 message functions | |
Number of login stations for message functions, max. | 16 |
Test commissioning functions | |
Diagnostic buffer | |
present | Yes |
Number of entries, max. | 3200 |
adjustable | Yes |
preset | 120 |
Configuration | |
Configuration software | |
STEP 7 | Yes; V5.0 SP2 |
Programming | |
Programming language | |
LAD | Yes |
FBD | Yes |
STL | Yes |
SCL | Yes |
CFC | Yes |
GRAPH | Yes |
HiGraph® | Yes |
Know-how protection | |
User program protection/password protection | Yes |
Dimensions | |
Width | 50 mm |
Height | 290 mm |
Depth | 219 mm |
Weights | |
Weight, approx. | 1070 g |
Status | Jul 7, 2014 |
The below specs apply to this product
Manufacturer | Siemens |
---|---|
Alternative Partnumber | 6ES7 414-4HJ00-0AB0 |
Range type | Processor Module |
---|---|
Range | Simatic S7-400 |
Here are some PDFs you can download