Siemens Simatic S5 IM308 interface module

For more information on how your data is processed and stored please read our privacy policy.

2 year warranty 2 year warranty*

Worldwide delivery Worldwide delivery

Returns accepted Returns accepted

*Manufacturer's warranty does not apply

Simatic S5 IM308 interface module
Description

About this product

Here is all you need to know

The Siemens 6ES5308-3UC21 links the PROFIBUS-DP to the CPUs in the Simatic S5-115U, S5-135U and S5-155U programmable controllers. The module is frequently referred to as the IM 308-C in the Siemens literature and provides:

  • Large address space (up to 13,300 bytes in all for input, outputs and diagnostics data, for addressing with FB IM308C)
  • Baud rates from 9.6 kbaud to 12 Mbaud
  • Freeze and Sync control commands
  • usable as DP master and/or DP Slave
The module is the direct replacement for the 6ES5308-3UC11 which is also referred to as the IM308-C. The new IM 308-C no longer permits programming of 12V memory cards. If you need this functionality, Northern Industrial is still able to provide these units. 
Memory card

The following memory cards can be used with the IM 308-C: 

Memory Size

Voltage

Order No.

Available

256 Kbytes

5V

6ES5 374-1KH21

yes

1 Mbytes

5V

6ES5 374-1KK21

yes

256 Kbytes

12V

6ES5 374-1FH21

no

512 Kbytes

12V

6ES5 374-1FJ21

no

Please note that the refubished IM 308-C is not supplied with a 5V memory card. 

If you try to program a 12 V memory card in a the 6ES5308-3UC21 with product version 1 and higher, the CPU and the IM 308-C will enter STOP mode. The "IF" LED will light up on the IM 308-C.

DesignationFunction

Backplane connectors X1 and X2

Blackplane connector X1 and X2 enable communication between the IM308-C and the CPU via the S5 I/O bus. 
Memory card All important configuration data for the IM308-C and bus layout is stored on the memory card.

Mode Selector Switch

(IM308-C as DP-Master)

RN (RUN): normal operation IM308-C read the inputs ofthe slave and sets the output

ST (STOP): IM308-C does not exchange data with the slaves, it may, however, receive the token (send authorization) from another master on the bus and pass on the token.

OFFL IM308-C does not exchange data with the slave and cannot receive the token (send authorization) from another master on the bus)

 

Mode Selector Switch

(IM308-C as DP-Slave)

 RN (RUN): normal operation; IM 308-C is DP slave and exchange data with the DP master

ST (STOP) or OFF: IM308-C is DP slave and does not exchange data with the DP master. No exchange of data between the IM308-C/DP slave and the slave CPU.

Depending on parameterization with COM Profibus QVZ or PEU is reported to the master CPU.

Bit ), station status 1, is set.

 LEDs The meanings of the LEDs are shown in table 3-2 and 3.3
 Profibus-DPThe bus connectors of the field bus connect to the IM308-C via the Profibus-DP 
 Jumper X10 Profibus-DP grounded or not grounded
 Jumper X9 PEU signal switched (power fail in expansion unit)

 

 
PDFs

The Specs

The below specs apply to this product

ManufacturerSiemens
Alternative Partnumber6ES5 308-3UC21
Range typeInterface Module
RangeSimatic S5
EAN4025515066439
PDFs

Looking for more details on this product?

Here are some PDFs you can download

Stopping downtime for over 40 years

Learn more about us

Northern Industrial We’ve come a long way since our small workshop in the 90s.
Northern Industrial Microsoft did a story on us after we were the first business in the whole of the UK to install Windows 2000 server.
Northern Industrial Back in the early 2000s we had a small group of engineers compared to over 40 today.
Northern Industrial We’re continuously developing our test facilities including the use of robots.
Northern Industrial Our current building is home to thousands of automation parts in Lancashire, England.
Northern Industrial Celebrating our 40th birthday in 2018 with John (centre) who started Northern Industrial back in 1978!