You will get en email confirming that we have received your enquiry.
2 year warranty*
Worldwide delivery
Returns accepted
*Manufacturer's warranty does not apply
You will get en email confirming that we have received your enquiry.
One of our team will be in touch to confirm your part(s) specification and condition.
You will receive a comprehensive quote tailored to your specific needs.
Here is all you need to know
The Mitsubishi A1SJ61BT11 is a control and communication link system master/local module to be used in conjunction with the Melsec A Series PLC CPU. A CC-Link system is used to connect distributed modules, such as I/O modules, special function modules and intelligent function modules, using dedicated cables so that they can be controlled by a programmable controller CPU. The A1SJ61BT11 has a number of features which are outlined in the performance specifications table below.
Part number | A1SJ61BT11 |
Transmission speed | 156kbps/625kbps/2.5Mbps/5Mbps/10Mbps selectable |
Maximum overall cable distance | It differes depending on transmission speed |
Maximum number of modules that can be connected (when master station) | 64 units However, the following conditions must be met: {(1 × a) + (2 × b)+ (3 × c) + (4 × d)} ≤ 64 a: The number of occupied modules by station 1. b: The number of occupied modules by station 2. c: The number of occupied modules by station 3. d: The number of occupied modules by station 4. {(16 x A) + (54 x B) + (88 x C)} ≤ 2304 A: Remote I/O station's numbers ≤ 64 B: Remote device station's numbers ≤ 42 C: Local station's, standby master station's and intelligent device station's numbers ≤ 26 |
Number of occupied stations (when local station) | 1 station or 4 stations (switched by DIP switch) |
Communication method | Poring method |
Synchronous method | Frame synchronous method |
Signed method | NRZI method |
Transmission path | Bus (RS-45) |
Transmission format | Conform to HDLC |
Error control system | CRC (X16+X12+X5+1) |
Cable | CC-Link dedicated cable/CC-Link dedicated high-performance cable |
RAS function | Auto return function Slave station cut off function Link special relay/Error detection by register |
Parameter entry numbers for E2PROM | 10000 times |
I/O occupied points number | 32 points (I/O allocation: special 32 points) |
Internal consumption current (5 VDC) | 0.4 A |
Weight | 0.25 kg |
The below specs apply to this product
Manufacturer | Mitsubishi |
---|---|
Range type | Interface Module |
Range | Melsec AnS Series |
---|
Here are some PDFs you can download